A voltage transformer (VT), also called a potential transformer in some systems, scales primary voltage to a lower secondary voltage for metering, protection, or control. Its burden is the electrical load connected to that secondary—not the primary circuit load. Identifying the burden helps buyers specify a VT suited to the devices and wiring it will serve, while preserving the accuracy required for the application. IEEE C57.13 addresses instrument-transformer performance and selection. ([standards.ieee.org](https://standards.ieee.org/standard/C57_13-2016.html))
Burden, Defined
Voltage-transformer burden is the load connected across its secondary winding, including the input load of every meter, relay, transducer, or other device, plus the effect of connecting leads and terminals. It is commonly expressed as apparent power in volt-amperes (VA) at a stated secondary voltage and frequency. In plain terms, burden describes how much work the attached circuit asks the VT to do. It is not the primary system’s total demand, and it is not simply the number of connected devices: different devices draw different amounts, and wiring adds to the total. For selection, gather the device input data and account for the complete secondary circuit. Then compare that connected burden with the VT’s applicable rated burden and accuracy information. The relevant rating and acceptable limits depend on the specific transformer and application, so verify them from manufacturer documentation and project requirements.
Why It Affects Accuracy
A VT is selected not only to produce a usable secondary voltage, but also to meet the application’s accuracy needs under its expected load. As burden changes, the transformer’s voltage ratio and phase relationship can deviate from ideal behavior. Those deviations matter differently by use: a metering circuit may have defined measurement accuracy needs, while a protective relay circuit must receive signals suitable for its intended protection function. A transformer’s accuracy designation therefore should be reviewed alongside its burden capability, rather than treated as a standalone label. Too much connected load can put operation outside stated performance conditions; a very light load may also be relevant where the manufacturer specifies performance over a particular burden range. Don’t assume a single accuracy class answers every question. Check the device requirements, expected connected VA, and the VT’s published performance conditions together before specifying or approving a selection.
What Belongs in the Calculation
Start with the secondary devices that will actually be connected, not a generic count of instruments. Request their burden or input-impedance information at the intended operating conditions, and note whether each device is continuously connected or switched into the circuit. Include the secondary wiring: lead resistance and the circuit arrangement can affect the load seen by the VT, particularly when wiring runs are long or multiple devices share a circuit. Consider terminal blocks, test switches, fuses, and other components where their electrical characteristics contribute to the secondary circuit. If the design may add instruments or relays later, identify that planned allowance explicitly instead of guessing at spare capacity. Keep the calculation traceable: list devices, relevant data, wiring assumptions, and the total estimated burden. A qualified electrical designer can confirm the method and applicable limits for the project; verify all input figures against current equipment documentation.
Selecting for the Application
Use the burden estimate to compare candidate VTs against the actual secondary voltage, system conditions, accuracy requirement, and intended function. Avoid choosing solely by a familiar VA figure: the acceptable burden range and accuracy performance must fit together for the specific model. Where measurement and protection devices share a secondary, confirm that the combined arrangement meets both functions’ requirements; separate circuits or transformers may be worth evaluating if their needs conflict. Also check practical details such as mounting, primary and secondary connections, insulation and environmental requirements, and how the transformer will be coordinated with the switchgear design. These are project-specific selection points, not assumptions about what any assembly includes. A procurement specification should state the required data and request confirmation of the selected VT’s suitability. For custom switchgear, Switchgear Builder Virginia can review project requirements and build to an agreed configuration; ratings, components, and schedules remain subject to quote and verification.
Questions to Resolve Before Ordering
Before finalizing a specification, confirm who supplies the VT and secondary devices, which devices share each secondary, and whether future additions are expected. Ask for the transformer’s rated burden and the conditions tied to its stated accuracy, then compare those values with a documented circuit calculation. Resolve the required secondary voltage, frequency, connection arrangement, and application with the responsible engineer. If drawings or device selections change, revisit the burden rather than carrying forward an outdated total. For a new switchgear project, provide the one-line diagram, metering and protection device information, and relevant performance requirements so the configuration can be reviewed against the intended use. Switchgear Builder Virginia manufactures in the USA using all-American components, offers custom builds and nationwide shipping, and can discuss short lead times; actual scope, ratings, and schedule must be confirmed in the quote.