A “35 kV” label is a starting point, not a complete equipment specification. For a new switchgear quote, identify the system’s nominal voltage, the required rated maximum voltage, insulation level, available fault current, and the devices the lineup must contain. Then classify the assembly by the applicable standard and construction type rather than relying on a sales label. Switchgear Builder Virginia manufactures custom equipment in the USA using all-American components, with schedules and ratings subject to quote and verification. Clear source documents help the manufacturer and project team resolve rating questions before the lineup is configured.
Name the voltage basis
Start with the system nominal voltage shown on the one-line diagram, then separately state the equipment’s required rated maximum voltage. A project described as “35 kV” may be referring to its nominal system class, while the equipment specification uses a different standardized maximum-voltage value. Do not assume the two numbers are interchangeable or choose a rating from the marketing label alone. Ask the engineer or utility to confirm the system voltage, grounding arrangement, frequency, and any operating conditions that affect selection. Provide the latest one-line and written specifications together, and identify which document governs if they differ. This avoids quoting a lineup around an informal shorthand that conflicts with the project basis. Switchgear Builder Virginia can use the confirmed requirements to develop a custom build; final equipment ratings remain subject to engineering review and quote.
Classify the assembly
State the intended construction and governing standard in the inquiry. For example, metal-clad switchgear with drawout electrically operated circuit breakers is not the same assembly category as metal-enclosed interrupter switchgear. IEEE publishes distinct standards for these categories, so a broad “35 kV switchgear” description alone does not tell a supplier which design basis to use. ([standards.ieee.org](https://standards.ieee.org/ieee/C37.20.2/11804/)) Confirm the required standard and edition with the project engineer, owner, or utility rather than selecting one based on a product name. Also describe the application: utility service, plant distribution, generator connection, or another duty. This context helps distinguish required switching and protection functions from optional preferences. The standard classification is a practical way to organize the specification, but it does not by itself confirm that a proposed lineup meets every project requirement.
Specify insulation and fault duty
Provide the required insulation level from the project documents, including the specified withstand values and any conditions relevant to the installation. Avoid substituting a familiar voltage label for the actual dielectric requirements; the nameplate and proposal should be checked against the approved specification. Separately provide the available fault current at the switchgear location, the source assumptions, and the required short-circuit and short-time withstand duties where specified. These figures affect equipment selection and coordination, and they should come from the engineer or utility’s system study—not a guess based on transformer size or an existing lineup. If the study is preliminary, mark it as such and identify who will confirm it. Ask the supplier to show the proposed ratings and applicable basis in the quote for review. Do not treat a component rating as proof of the complete assembly’s rating.
List devices and lineup needs
Describe each required incoming, tie, feeder, and metering position, along with the switching or interrupting device assigned to it. Identify circuit breaker, interrupter switch, fuse, relay, control power, instrument transformer, metering, and communications requirements where applicable. State which functions are mandatory and which are options under review. This distinction matters because device choice, protection scheme, compartment arrangement, and control interfaces can change the lineup design. Include bus configuration, continuous current requirements, cable entry and termination expectations, physical constraints, and known interface points, but have the project engineer verify the details. Attach approved drawings and note unresolved items rather than silently filling gaps. A complete device schedule lets a custom manufacturer assess the requested arrangement and flag information needed before a firm equipment configuration can be quoted.
Build a verifiable quote basis
Send the inquiry as a concise rating package: nominal voltage, rated maximum voltage, insulation level, available fault current, required devices, governing standard, and supporting project documents. Add environmental and installation conditions that the specification identifies, plus the requested documentation and any acceptance or inspection requirements for confirmation. Ask the proposal to identify the offered assembly type, ratings, device arrangement, assumptions, and exceptions so reviewers can compare it directly with the design basis. If a requirement is missing or contradictory, resolve it with the responsible engineer before treating a selection as final. Switchgear Builder Virginia provides direct USA manufacturing, custom builds, and nationwide shipping; quoted schedules and ratings require confirmation for the specific order. The goal is a new lineup whose documented configuration can be checked against the project specification, not a selection made from a label alone.