AMERICAN BUILT. PROJECT READY.MANUFACTURER DIRECT (951) 403-5738
Gray switchgear with meters and circuit breakers inside an open enclosure.

COMPARISONS / VIRGINIA & NATIONWIDE

Metal-Clad vs Metal-Enclosed Switchgear

New American-built power distribution equipment, engineered around your project.

ENGINEERED FOR POWER
US
Made in the USAAmerican components
✓
Project-specific standardsConfirmed for equipment type
↗
Built to moveLead time quoted by project

COMPARISONS / MANUFACTURER DIRECT

Metal-clad and metal-enclosed switchgear are not interchangeable labels for one construction. The distinction affects how equipment is divided internally, which switching devices it can use, and what maintenance or operating plan may fit the project. Metal-clad describes a defined medium-voltage construction; metal-enclosed covers a broader class of assemblies and does not, by itself, mean low voltage. Switchgear Builder Virginia builds new equipment to project requirements, with ratings and configuration subject to quote and verification. Compare the required voltage class, device arrangement, protection functions, and applicable product standard before choosing a lineup.

Start With the Equipment Class

Metal-clad is a specific medium-voltage switchgear category, not a general synonym for any steel-enclosed electrical assembly. IEEE C37.20.2 describes metal-clad equipment with drawout electrically operated circuit breakers and grounded metal barriers that compartmentalize components such as the bus, instrumentation, and connections. Metal-enclosed is broader wording: particular metal-enclosed assemblies may use different devices and internal arrangements. The phrase alone does not establish voltage class, breaker construction, or degree of separation. This distinction matters when a project specification names a construction type: substituting a different category based on appearance or a broad product label can leave device interfaces, protection coordination, or documentation unresolved. Identify the system voltage and the exact equipment category first, then confirm the applicable standard and construction in the equipment submittal. ([standards.ieee.org](https://standards.ieee.org/ieee/C37.20.2/11804/))

Compare Compartmentation

Compartmentation changes what sits behind each access door and how components are separated by grounded barriers. In metal-clad construction, the defined barrier arrangement separates major primary components, including bus and connections, rather than relying only on a shared outer enclosure. Other metal-enclosed designs can have their own partitions, but the phrase “metal-enclosed” does not promise the same internal boundaries. Buyers should compare the lineup drawings, identify bus and cable compartments, and ask which barriers separate energized sections from breaker or control spaces. Also check whether the proposed arrangement matches the project’s operating and maintenance plan; an enclosure label cannot answer that on its own. More separation can affect lineup dimensions, access, and configuration choices, while a simpler arrangement may serve a different application. Treat compartment design as a specified feature to review, not an assumed consequence of the word enclosed. ([standards.ieee.org](https://standards.ieee.org/ieee/C37.20.2/11804/))

Check Device Movement

Drawout describes a device arrangement in which a circuit breaker can move between defined positions within its section; it does not mean the whole lineup is mobile or that every metal-enclosed assembly uses a drawout breaker. Metal-clad medium-voltage equipment is associated with drawout electrically operated breakers, while broader metal-enclosed assemblies may use stationary breakers, interrupter switches, fuses, or other permitted combinations, depending on the equipment category and specification. A drawout approach can support a planned way to isolate or access a breaker, but it also brings questions about cell geometry, interlocks, racking provisions, and compatible replacement devices. Fixed-device arrangements may change space use and maintenance planning. Compare the actual device schedule and manufacturer drawings, not just a sales label. Confirm the intended breaker or switch type, operating method, interlocks, and any required spare-device strategy before finalizing the lineup. ([standards.ieee.org](https://standards.ieee.org/ieee/C37.20.2/11804/))

Match Protection to the System

Protection choices follow the power system and selected switching devices, not simply the enclosure name. A design may use protective relays with circuit breakers, or fuses coordinated with an interrupter switch, depending on the application and specification. The engineer should establish fault levels, load and transformer data, grounding method, coordination objectives, and any required metering or control functions. Those inputs help determine device ratings and relay settings; they should not be guessed from a comparison page or copied from a different installation. Ask suppliers to show how proposed breakers, fuses, relays, and instrument transformers fit the one-line diagram and control scheme. Review trip and alarm functions, available control power, and interface requirements as applicable. A different device arrangement can affect selectivity, operating procedures, and maintenance needs, so resolve protection responsibilities and setting review with the project’s qualified engineering team before equipment release.

Verify Standards and Scope

Applicable standards depend on the exact equipment type and voltage class. IEEE C37.20.2 addresses metal-clad switchgear; IEEE C37.20.3 addresses metal-enclosed interrupter switchgear rated above 1 kV AC through 48.3 kV AC. Neither label means every product called metal-enclosed has the same construction or scope. Low-voltage switchboards are a separate product category, and UL 891 applies only to applicable low-voltage switchboards—not medium-voltage metal-clad or metal-enclosed switchgear. Put the required standard, voltage, continuous-current and interrupting ratings, enclosure and device arrangement, and documentation into the request for quote. Confirm each rating and any required listing or approval against the quoted configuration and project documents. Switchgear Builder Virginia manufactures new custom equipment with direct USA manufacturing, all-American components, and nationwide shipping; configuration, applicable standards, and schedule remain subject to quote and verification. ([standards.ieee.org](https://standards.ieee.org/ieee/C37.20.2/11804/))

Related project guides

START A CONVERSATION

Let’s build the right solution.

Tell us what you’re building, replacing or upgrading. Share the information you have now; project details and availability can be confirmed together.

PREFER TO TALK?

(951) 403-5738

Virginia projects. Nationwide delivery.

This attempts to open a draft in your configured email app; review and send it there. Browser support varies. For immediate assistance, call (951) 403-5738.

Request a quote